Allen Bradley MicroLogix 1500 Programmable Controller Base Unit: 1764-24BWA

Allen Bradley MicroLogix 1500 Programmable Controller Base Unit: 1764-24BWA

In stock. Usually ships in 5 - 7 working days.
Part Number:1764-24BWA
You need to be a registered customer to view price or order this product. Please Login to your Account or Click Here to Register.
Safe and Secure
Part Number : 1764-24BWA

Model1764-24BWA
Number of I/O

12 inputs
12 outputs
Line Power85 to 265V ac at 47 to 63 Hz
Power Supply Usage
88 VA
Power Supply Inrush

120V ac = 25A for 8 ms
240V ac = 40A for 4 ms

User Power Output

24V dc at 400 mA, 400 μF max.
Input Circuit Type24V dc, sink/source

Output Circuit Type

relay
Typical CPU Hold-up Time
10 to 3000 ms
Operating Temp.+0°C to +55°C (+32°F to +131°F) ambient
Storage Temp.-40°C to +85°C (-40°F to +185°F) ambient¹
Operating Humidity5% to 95% relative humidity (non-condensing)

Vibration

Operating: 10 to 500 Hz, 5G, 0.030 in. max. peak-to-peak
Relay Operation: 2G
Shock (without Data Access Tool installed)

Operating: 30G panel mounted (15G DIN Rail mounted)
Relay operation: 7.5G panel mounted (5G DIN Rail mounted)
Non-Operating: 40G panel mounted (30G DIN Rail mounted)
Shock (with Data Access Tool installed)


Operating: 20G panel mounted (15G DIN Rail mounted)
Relay operation: 7.5G panel mounted (5G DIN Rail mounted)
Non-Operating: 30G panel mounted (20G DIN Rail mounted)
Agency Certification



UL 508
C-UL under CSA C22.2 no. 142
Class I, Div. 2, Groups A, B, C, D (UL 1604, C-UL under CSA C22.2 no. 213)
CE/RCM/EAC compliant for all applicable directives
Electrical/EMC








The module has passed testing at the following levels:
EN61000-4-2: 4 kV contact, 8 kV air, 4 kV indirect
EN61000-4-3: 10 V/m
EN61000-4-4: 2 kV, 5 kHz; communications cable: 1 kV, 5 kHz
EN61000-4-5: communications cable1 kv galvanic gun
           -I/O: 2 kV CM, 1 kV DM,
           -Power Supply (1764-24AWA/1764-24BWA): 4 kV CM, 2 kV DM
           -Power Supply (1764-28BXB): 0.5 kV CM, 0.5 kV DM
EN61000-4-6: 10V, communications cable 3V
Terminal Screw Torque1.13 Nm (10 in-lb) rated; 1.3 Nm (12 in-lb) maximum
Programming Software


For 1764-LSP Series A Processors: RSLogix 500, Version 3.01.09 or higher
For 1764-LSP and 1764-LRP Series B Processors: RSLogix 500, Version 4.00.00 or higher.

(1) Recommended storage temperature for maximum battery life (5 years typical with normal operating/storage conditions) of the 1764-RTC, 1764-MM1RTC, 1764-MM2RTC, 
     and 1764-MM3RTC is -40°C to +40°C (-40°F to +104°F). Battery life is significantly shorter at elevated temperatures.