Allen Bradley  Flex I/O Analog Input Module: 1794-IE8

Allen Bradley Flex I/O Analog Input Module: 1794-IE8

Your Price:$524.00
Retail Price:$616.00
You Save:$92.00(15%)
In stock. Usually ships in 5 - 7 working days.
Part Number:1794-IE8
You need to be a registered customer to view price or order this product. Please Login to your Account or Click Here to Register.
Safe and Secure
Part Number: 1794-IE8

Technical Specifications
  • Terminal Base Screw Torque: 
    7 pound-inches (0.8Nm)
    9 pound-inches (1.0Nm) for 1794-TBN
  • Isolation Voltage: 
    Tested at 850V dc for 1s between user power to system
    No isolation between individual channels
  • External dc Power Supply
    Voltage Range: 
    24V dc nominal
    10.5 to 31.2V dc (includes 5% ac ripple)
    Supply Current: 60mA @ 24V dc; 150mA @ 12V dc
  • Dimensions (with module installed): 31.8H x 3.7W x 2.1D inches (45.7H x 94W x 53.3D mm)
  • Flexbus Current: 20mA
  • Power Dissipation: 3.0W maximum @ 31.2V dc
  • Thermal Dissipation: Maximum 10.2 BTU/hr @ 31.2V dc
  • Keyswitch Position: 3
  • Environmental Conditions
    Operating Temperature:
    IEC 60068-2-1 (Test Ad, Operating Cold),
    IEC 60068-2-2 (Test Bd, Operating Dry Heat),
    IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
    0 to 55°C (32 to 131°F)


    Storage Temperature:
    IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),
    IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat),
    IEC 60068-2-14 (Test Na, Un-packaged Non-operating Thermal 
    Shock):
    40 to 85°C ( 40 to 185°F)


    Relative Humidity:
    IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat):
    5 to 95% non-condensing

    Vibration:
    IEC60068-2-6 (Test Fc, Operating):
    5g @ 10-500Hz

    Shock:
    IEC60068-2-27 (Test Ea, Unpackaged shock):
    Operating 30g
    Non-operating 50g

    Emissions:
    CISPR 11
    Group 1, Class A (with appropriate enclosure)

    ESD Immunity:
    EC 61000-4-2:
    4kV contact discharges
    8kV air discharges

    Radiated RF Immunity:

    IEC 61000-4-3:
    10V/m with 1kHz sine-wave 80%AM from 30MHz to 1000MHz

    Conducted RF Immunity:
    IEC 61000-4-6:
    10V rms with with 1kHz sine-wave 80%AM from 150kHz to 30MHz

    EFT/B Immunity:
    IEC 61000-4-4:
    ±2kV at 5kHz on signal ports

  • Availability: In Stock
  • Estimated Lead Time: Usually Ships in 5 - 7 Working Days
  • Shipping Weight: 2 Kg