Ordering Information
  • Model: ST5484E - Seismic Velocity 4-20 mA Velocity Transmitter
  • Full Scale Range¹: 1511.0 in/sec (25.4 mm/s) true RMS
  • Housing Material & Stud Size¹: 1303 SS housing, ½” NPT stud
  • Hazardous Area Certification2,3,4: 3ATEX, EEx ia IIC T4 Ga (intrinsically safe)
  • Connection Type2: 2Terminal Block, 2-wire6 ; (4-20 mA output only)
  • High-Pass Filter: XCustom (consult factory)5 
  • Low-Pass Filter: XCustom (consult factory)5
  • M1370

NOTES:
  1. The ST5484E uses an RMS amplitude detection circuit. Full scale ranges in peak units use scaled RMS (i.e., RMS x v2). The “derived peak” measurements will equal true peak only under the special case of a pure sinusoid, not complex vibration signals.
  2. Hazardous Area Certifications are not compatible with all connection types. Consult Table 3 for allowable combinations of C & D options.
  3. Some approvals require intrinsic safety barriers, others require Explosion-Proof wiring practices.
  4. ATEX/IECEx/INMETRO Ex d (flameproof) approvals (ordering option C=8 or C=6) require conduit elbow 8200-AAA-IEC, sold separately.
  5. High- and Low-Pass filter corners for standard filters must be separated by at least one octave (low-pass frequency must be at least twice the high-pass frequency). All combinations are allowed except E = 6 and F = 4, 5, or 6. Custom filters with closer separation and/or different roll-offs may be available in some instances. Consult the factory if custom filters are required.


  • Estimated Lead Time: 3 - 5 Weeks
  • Shipping Weight: 2 Kg